State-variable control of shunt FACTS devices using phasor measurements

J. Machowski, J. W. Bialek

Research output: Contribution to journalArticlepeer-review

24 Citations (Scopus)

Abstract

This paper addresses the problem of state-variable stabilizing control of power system using shunt FACTS devices. This stabilizing control is activated in the transient state of a power system and is supplementary with respect to the main steady-state control of a FACTS device. Stabilizing control laws have been derived for a non-linear multi-machine system model using direct Lyapunov method with the aim to maximize the rate of energy dissipation during power swings and therefore maximization of damping. The proposed control strategy is executed by a non-linear multi-loop controller with rotor angles and speed deviations of synchronous generators used as the input signals. The input signals, obtained from a phasor measurement system, are necessary only from a small area around the controlled shunt FACTS device. Validity of the proposed state-variable control has been confirmed by computer simulation for a small multi-machine test system.

Original languageEnglish
Pages (from-to)39-48
Number of pages10
JournalElectric Power Systems Research
Volume78
Issue number1
DOIs
Publication statusPublished - Jan 2008
Externally publishedYes

Keywords

  • FACTS
  • Phasor measurements
  • Power system
  • Stabilizers
  • Transient stability

Fingerprint

Dive into the research topics of 'State-variable control of shunt FACTS devices using phasor measurements'. Together they form a unique fingerprint.

Cite this