Adaptive underfrequency load shedding integrated with a frequency estimation numerical algorithm

V. V. Terzija, H. J. Koglin

Research output: Contribution to journalArticlepeer-review

46 Citations (Scopus)

Abstract

An approach to adaptive underfrequency load shedding, a procedure for protecting electric power systems from dynamic instability and frequency collapse, is presented. It consists of two main stages. In the first stage, the frequency and the rate of frequency change are estimated by the nonrecursive Newton type algorithm. By using the simplest expression of the generator swing equation, in the second stage the magnitude of the disturbance is obtained. The UFLS plan is adapted to the magnitude estimated, to obtain a more efficient system for operation during emergency conditions. Results of procedure testing are demonstrated through computer simulations by using a 10-machine New England test system.

Original languageEnglish
Pages (from-to)713-718
Number of pages6
JournalIEE Proceedings: Generation, Transmission and Distribution
Volume149
Issue number6
DOIs
Publication statusPublished - Nov 2002
Externally publishedYes

Fingerprint

Dive into the research topics of 'Adaptive underfrequency load shedding integrated with a frequency estimation numerical algorithm'. Together they form a unique fingerprint.